AEMC 2620 Leakage Current Clamp Probe, 500 µA to 400 A, 4.4 in Jaw

AEMC 2620 Leakage Current Clamp Probe, 500 µA to 400 A, 4.4 in Jaw

$349.00
Skip to product information
AEMC 2620 Leakage Current Clamp Probe, 500 µA to 400 A, 4.4 in Jaw

AEMC 2620 Leakage Current Clamp Probe, 500 µA to 400 A, 4.4 in Jaw

$349.00

AEMC 2620 Leakage Current Clamp Probe, 500 µA to 400 A, 4.4 in Jaw

Overview

The detector is a highly sensitive nickel alloy AC current transformer that locates insulation faults and leakage to ground on live circuits without shutting equipment down. It works on single, dual and three-phase networks and can clamp large or multiple conductors.

Accuracy is ±3% of reading ±1 mV at the low end of the 4 A range and ±0.35% of reading on the 400 A range, over 48 to 1000 Hz. The probe meets EN 61010-2-032 at 600 V CAT III, weighs 1.3 kg and operates from -10 to 55 °C.

Features

  • Leakage or differential current from 500 µA
  • Current up to 400 A continuous duty
  • Two ranges: 4 A (1 mV/mA) and 400 A (1 mV/A)
  • Large 4.4 in (112 mm) jaw opening
  • Connects directly to DMMs on mV or VAC range
  • Single, dual and three-phase networks
  • 600 V CAT III, EN 61010-2-032

Applications

  • Locating insulation breakdown and ground faults
  • Leakage analysis on grounding conductors and ground loops
  • Preventive maintenance on high current loads

AEMC 2620 Leakage Current Clamp Probe, 500 µA to 400 A, 4.4 in Jaw Technical Specifications

Current range, 4 A range 500 µA to 4 A
Current range, 400 A range 500 mA to 400 A
Output signal 1 mV/mA (4 V max) / 1 mV/A (400 mV max)
Accuracy, low end ±3% of reading ±1 mV (500 µA to 10 mA)
Accuracy, 400 A range ±0.35% of reading ±1 mV (100 to 400 A)
Frequency range 48 to 1000 Hz
Load impedance 1 MΩ min
Jaw opening 4.4 in (112 mm)
Safety rating EN 61010-2-032, 600 V CAT III
Dimensions 285 x 175 x 45 mm
Weight 1.3 kg (2.87 lb)
Operating temperature -10 to 55 °C, up to 85% RH non-condensing

Manufacturer information: Model 2620 on aemc.com.